Hello Wizard,
Ethernet via Standard TCP connection from Laptop directly to SAFEX-C.1x is not possible to the primary and secondary Ethernet.
Two different Ethernet connections are possible when the fieldbusses are running: 1. EtherCAT on primary port XF28/29 connected to a CORE control. --> EoE connection via the CORE is possible refer HowTo: ctrlX Safety Engineering remote access to SAFEX-C1x via EoE (Engineering over Ethercat) (for Bosch Rexxroth Laptop in Bosch-Networks the following command has to be set additional to the route: netsh int tcp set global timestamps=disabled) 2. Ethernet connection via PROFINET interface on secondary port XF30/31. The IP-channel has to be configured in the PN-Controller refer HowTo: ctrlX SAFETY Engineering remote access to SAFEX-C.15 via Profinet
please give me a call ChrM