I am trying to write P-0-0858, Data of external braking resistor to a SoE drive. I found this post about doing it with CoE. I came up with what I think are the correct values, but when I put them into TwinCAT the values are not written. Does anyone have any experience with this?
Solved! Go to Solution.
07-03-2023 06:23 PM
You have to write:
<InitCmd>
<Transition>PS</Transition>
<Comment><![CDATA[Bremswiderstand extern: Typdaten]]></Comment>
<Timeout>0</Timeout>
<Data>f0490200002d310190e71400</Data>
<IDN>33626</IDN>
<OpCode>3</OpCode>
<Elements>64</Elements>
<Attribute>0</Attribute>
<DriveNo>0</DriveNo>
</InitCmd>