To question 1: No, this needs not to be considered. To question 2: For these-Stop input a normal PLC output is good enough, for the STO input it must be a dynamized signal. To question 3: If the customer uses a safe output (normally he then should use a double output) he doesn’t need a relay in between but connects that directly.