In the following we show you how to use ctrlX CORE with ELMO Drive.
Versions used All the functions and screen shots are based on:
Engineering: ELMO Application Studio EAS II version 2.8.1.6 64Bit
ELMO Platinum Drive Harmonica 02.00.03.00 B07 19Oct2021
ELMO Platinum Drive Twitter 02.00.03.00 B07 19Oct2021
ctrlX CORE version 1.20
ctrlX WORKS 1.20
Prerequisites
A connection to the ctrlX CORE has been successfully established (Browser), the device is correctly wired, and 24 V are successfully put on. As well as the Engineering tool ctrlX WORKS Engineering has been started, and the EAS II (ELMO Application Studio) has been installed and started.
1. What is the target of this description
Show configuration of EtherCAT CoE and Motion app with ctrlX WORKS to get a running system with ELMO drive.
2. What is required
actual device description file from ELMO drives (actual version ElmoPlatinum_10_V120027_S.xml)
installed EtherCAT Master App, Motion App and PLC App on the ctrlX CORE
3. Configuration of IO Engineering
Open "Device Repository" Open Device Repository
Install device description file Install device description file
Scan device and insert in project IO Engineering Scan devices
Download IO configuration to ctrlX CORE Download configuration to Core IO Engineering Startup
Check the startup parameters, to use the Cyclic synchronous Position (CSP) operation mode (ELMO operation mode "Position = 5").
4. Configuration of ctrlX CORE, Axis Profile and Motion
Add Axis profile, enter a name, select CANopen over Ethercat Add axis profile
Map the variables from the drive to the axis profile Core axis profile variables mapping Core axis profile mapping details drive!! Important !! Open the profile over the Data Layer to make the Scaling configuration of this drive.
You can check the resolution information with the ELMO Application Studio, see screenshot below. This drive doesn´t support the scaling objects (optional) that the ctrlX CORE motion normally needs. In this case you have to make the scalings inside the control. Check settings Data Layer settings 1 Data Layer settings 2
Add a Motion axis and connect the axis to the profile You can later change the format or the limits and so on, but these must match with the drive parameterization.
Add motion axis connect profile
Switch the motion in running mode Switch the motion in running
5. Create and check settings of ELMO drive
Start the ELMO Application Studio and Connect the drive Load ELMO application suite
Check the scaling and modulo parametrization Check scaling Check modulo behaviourHint: If you want to command the axis by ELMO Application Studio you must switch the parameter "af", see screenshot. Switch parameter "af"
6. Run the Motor (via Motion App)
Step 1: Run motor via Motion App
Step 2: Run motor via Motion App Hint: If this is working you can start with your PLC program.