Hello,
I can't find in the current documentation the allowed peak current per channel for the 4-channel digital output terminal (24 VDC, 2 A), 2-wire.
Anybody who knows where to find ?
Solved! Go to Solution.
04-21-2023 10:41 AM
Hello,
the data sheet is in preparation, each channel upto 2A, the sum curent over all channels 8A. short peak 2,6A
11-13-2023 03:51 PM - edited 09-03-2024 08:45 AM
Document can be found in our official online documentation.
Each channel upto 2A, the sum curent over all channels 8A. short peak 2,6A