Hello, As told I was occupied with other activities. But last week and this week I had some time to figure out one and other! When I used the CoDeSys ProfiNet controller wit a ctrlsX Drive it worked in no mater of time:) But when I used the HMC in combination with the proposed GSDML files it didn't work! So what I did I tried some other combinations of firmware in the HMC and GDSML files. And now i got my system working! In my HMC I use firmware "FWA-HYDRV*-20V24.30-D5-1-SRV-ML". The GDSML file that I use now is "GSDML-V2.25-Bosch Rexroth AG-011F-HydraulicDrive_01V01-20180907.xml"! And now I have data excange. When is use the proposed file "GSDML-V2.4-Bosch_Rexroth_AG-011F-HydraulicDrive_03V00-20210608.xml" the system gives me some errors and when I add the HMC to my project I can't delete the HMC from my project anymore. The only way to get out was close my project without saving and re-open the old project again! I'm writing a document with my exepriences and will add this to this item later on.