Hello,
we are working on a improvement for this topic.
For explanation: The buscoupler provides 8 A to the Up (Peripheral) voltage path. In the configurator we are calculating with a maximum load at each digital Output (0.5A / channel) --> In total 8A for all 16 channels. The DI module also consumes a 1 digit mA value from this path. To balance the power result, the configurator inserts the booster terminal.
We will update the database in short term and with future updates we will extend the possibilities with channel-specific parameterization of the connected load.
Best Regards
Thomas