Hello Max1, ok - the PLCprogr leads to a PLC_Exception: here some useful info to identy the rootcause. 1)Have a look in the PLC_diagnosis logger - but in case of an exception there is most like no entry , but have a look anyway.
2) Explore the correspoding log-file. ...scroll to the last one ...
3) You can activate the CallStack Viewer... in case you can trigger the topic or the "malfunction" rises for sure you can locate as soon the exception is rising. Double click and the viewer displays the point of no .. continue. 4) insert some check-functions provides by the rightclick wizzard...include template files.
Hope that helps as well:
https://docs.automation.boschrexroth.com/doc/3540156664/exception-handling/latest/en/
Bye
... View more