08-17-2023 11:23 AM - edited 08-17-2023 11:33 AM
Good morning,
i want to backup following parameter fields
S-0-0026
S-0-0027
S-0-0328
S-0-0329
I made a backup of all drive parameters. Then i delete all lines, i dont need.
When restoring, drive engineer tells me "2 S-0-0026.0.0 Operating data transmission too long" for S-0-0026 and also 27.
Even with a complete untouched parameter backup, drive engineer can not load these parameters.
I hope you can tell me, what's wrong. Attached you will find the .par file
Drive Engineer is Build: 1.24.0
Solved! Go to Solution.
08-17-2023 11:59 AM - edited 08-17-2023 12:00 PM
08-17-2023 07:26 PM - edited 08-17-2023 07:27 PM
Thank you, that worked for 90%. 🙂
At one drive, we had problems. In our .par file, we had "32" after the -- lines.
But at one drive, it could read the .par file. After checking it, it hat "64" in the lines after "--".