Hi Community,
I have upgraded my PLC project from version 1.20 to 2.6.6.
My arAxisStatus_gb is not working properly.
I cant get Torque and Velocity Value (See attached)
After E-STOP and resetting the Drive the arAxisStatus_gb unable to update Drive Mode_AB.
arAxisStatus_gb[1].Data.DeviceStatus.Home is not being updated after i clear reference point it remain true.
Please help.
Warmest regards,
Solved! Go to Solution.
2 weeks ago
Hello
please add the cyclic AT Telegram reganrding Torque and Speed (S40/S84) and map the signals in the axisprofil toward the motion.
This is going to solve the issue.