FORUM CTRLX AUTOMATION
ctrlX World Partner Apps for ctrlX AUTOMATION
Friday
Hi,
During commissioning of a machine mains fuse occassionally blew when XG31:3 got the signal to start loading DC bus (P-1720.0.150). Configuration is pretty similar to the picture with XCS/XMD/XMS.
After changing "Reaction to DC bus undervoltage" settings from E2026 to F2026, this problem no longer occured. I have no idea why this would have such an effect, so all suggestions are welcome.