Hello, when I try to show 64bit integer PLC values like “LINT” (correlates "Int64" for OPC UA) or “ULINT” and “LWORD” (correlates "UInt64" for OPC UA), the value is not shown correctly. The last 4 digits seems to be rounded when I try to use values near the type defined maximum for these data types. The LINT PLC value “-9223372036854775808” is shown as “-9223372036854776000”. The ULINT and LWORD PLC value “18446744073709551615” is shown as “18446744073709552000”. When I enter the value "-9223372036854775808" into the input field for the LINT value, the correct value "-9223372036854775808" is written into the PLC, but the HMI shows “-9223372036854776000". 32bit and 16bit Integer values are shown correct, even I reach the maximum value for these data types.