Hi @bclapperton, Happy I could help. Regarding the EDM improvments, if you see the block properties: You will be able to separate certain blocks into different reset groups, that you can safely reset without having to restart the logic. For this reset you will be able to use the Start/Reset Input Element as "Use as Block-Reset", but this is not implemented yet. Regarding the reset fieldbus, there is the function block "Reset from Network": However, this block still has very limited operation on the current release: It can only be used when SAFEX-C.1x is FSoE Slave or PROFISAFE Slave. Only works as "Use as Alarm Reset" (Resets all logic). Only works if it is connected to bit 0 of the F-Bus Input block. Given our current timetable my recommendation is to build your project witout expecting these fixes soon. Best Regards, BRamos